SF4 series
Technical data
No. of phase | 3 |
Circuit type | III |
Protection class | I |
Rated voltage (V) | 500 AC |
Rated frequency (Hz) | 5-150 |
Rippled frequency (kHz) | 4-16 |
L tolerance (%) |
± 10 ( differential mode ) ± 20 ( common mode ) |
C1, C2 tolerance (%) | ± 20 |
Test voltage (kV) |
2.0 DC Line-Line 2.0 DC Line-case |
Description of load | Symmetrical load of motors |
Operating conditions
Protection index |
IP XX B SF4-CD006-500-2 - SF4-CD046-500-2 IP XX A SF4-CE065-500-2 IP 00 SF4-CD006-500-0 - SF4-CE165-500-0 |
Ambient temperature [ °C ] | -10 …. +45 |
Storage temperature [ °C ] | -25 …. +70 ( EN 60721-3-1 ; 1K3 ) |
Transport temperature [ °C ] | -40 …. +85 ( EN 60721-3-2 ; 2K3 ) |
Overload capability | 1.5 times rated current for 1 minute per hour |
Climatic category | 25/085/21 ( EN 60068-1 ) |
Humidity |
3K3 (Without condensation, medium relative humidity 85%) |
Class of flammability | UL 94V-2 or better |
Class ISO °C VDE | H ( 180°C ) |
Class ISO °C UL | Class 180 |
Type of cooling | AN |
Operating conditions | DB |
Parallel connection | Yes (90% Single load) |
Overvoltage category | 3 >2000m = 2 ( EN 61800-5-1 ) |
Vibration resistance | Transport 2M2 ( IEC/EN 60721-3-2 ) |
Degree of pollution | 2 ( EN 61800-5-1 ) |
MTBF [h] | > 500.000 @ 45°C / 400V |