High Harmonic Filter (2-9 kHz)
High harmonic filter for reduction of the high harmonic distortion of active rectifiers.
Harmonic Mitigation of Harmonics 30th to 180th order (1.5kHz to 9kHz)
Reducing the distortion created between 2-9kHz to protect devices with capacitor sin such as Cap banks, Power Supplies and also anything with Inductance or Resistance, generated by devices like AFE’s, AIC’s and similar technology.
Product type |
High harmonic filter for reduction of the high harmonic distortion ( above 1.5kHz) of e.g active rectifiers. |
Type code |
HHF 160-400-50-20-A |
Topology |
Trap filter |
Order code |
25000013 |
Supply voltage |
3 • 400V (+ /-10%) |
|
50Hz (+/- 2%) |
Compensation |
Harmonic Mitigation of Harmonics 30th to 180th order |
Rated current |
24 A |
Ambient | |
Standards and requirements |
IEC/EN 61000-2-2 / -4 |
|
IEC/EN 61000-3-2 / -4 / -12 |
|
IEEE 519-2014 |
|
G5/4 |
Humidity |
Humidity class F without condensation 5…..85% – Class 3K3 (non-condensing) during operation |
Ambient temp. |
min. 5°C (41°F) max. 45 °C (113°F) |
|
derating = -2%/K between 45°C (113°F) and 50°C (122°F) |
Altitude |
<1000m |
|
derating above 1000m: -5%/1000m (up to 4000m) |
Specific data | |
Power loss |
360W |
Weight |
29kg |
Electrical connections, controls and auxilay supply |
|
Main supply |
Terminals 0,4…4mm² |
|
Tightening torque, min-max.: 1.5-1.8Nm |
Control |
Overtemperature NC contact Terminal A/B |