High Harmonic Filter (2-9 kHz)

High harmonic filter for reduction of the high harmonic distortion of active rectifiers.

Harmonic Mitigation of Harmonics 30th to 180th order (1.5kHz to 9kHz)

Reducing the distortion created between 2-9kHz to protect devices with capacitor sin such as Cap banks, Power Supplies and also anything with Inductance or Resistance, generated by devices like AFE’s, AIC’s and similar technology.

Product type

High harmonic filter for reduction of the high harmonic distortion

( above 1.5kHz) of e.g active rectifiers.

Type code

HHF 160-400-50-20-A

Topology

Trap filter

Order code

25000013

Supply voltage

3 • 400V (+ /-10%)

 

50Hz (+/- 2%)

Compensation

Harmonic Mitigation of Harmonics 30th to 180th order

Rated current

24 A

Ambient 

Standards and requirements

IEC/EN 61000-2-2 / -4

 

IEC/EN 61000-3-2 / -4 / -12

 

IEEE 519-2014

 

G5/4

Humidity

Humidity class F without condensation

5…..85% – Class 3K3 (non-condensing) during operation

Ambient temp.

min. 5°C (41°F)     max. 45 °C (113°F)

 

derating = -2%/K

between 45°C (113°F) and 50°C (122°F)

Altitude

<1000m

 

derating above 1000m: -5%/1000m (up to 4000m)

Specific data

Power loss

360W

Weight

29kg

Electrical connections, controls and auxilay supply

Main supply

Terminals 0,4…4mm²

 

Tightening torque, min-max.: 1.5-1.8Nm

Control

Overtemperature NC contact Terminal A/B

 