pattern

Comsys ADF P100

The ADF P100 active filter gives you everything in a compact format. Although compact and cost-effective, the ADF P100 features the same excellent cutting-edge performance as its bigger ADF P300 family member.

Like its bigger brother, the ADF P100 is ultra-efficient and easy to use. However the wall mounted format gives a more cost-effective packaging and allows the use of ADF technology in applications the ADF P300 cannot access. 

The ADF P100 has a nominal compensation current of 70 to 130 A RMS (three wire, 480V), 100 A RMS (four wire, 415V), and 90 A RMS (three wire, 690V). It is available in the voltage ranges 208 – 690 V RMS nominal, four wire up to 415 V RMS. The tall and narrow design allows the ADF P100 to be used in applications where space is at a premium.

The ADF P100 can be commissioned using the Web User Interface (WUI) called ADF Dashboard.  No special software needs to be installed on the laptop to perform commissioning, all that is needed is a laptop with an ethernet port and an ethernet cable and a recent web browser.

The new optional HMI-3 provides a graphical interface for commissioning, operation and systems management. Standard equipment is an indicator button which can start and stop the system. The HMI-3 is a new, optional, graphical HMI with color touch screen display.

In addition to the WUI, you can interface to the standard hardware using Modbus TCP (license key is required). You can start/stop the system, read out power quality data, and change control parameters and settings via fieldbus. The flexible functionality allows integration to overlying control such as a PLC or SCADA systems. The overlying system can change control parameters, or change compensation sets on the fly. This is useful in for example marine- and generator applications.

Other fieldbus interfaces (such as Profibus, Profinet) are available on request.

Each ADF P100 active filter is customized to maximize performance in each application. The common features that all systems share include:

APPLICATION FEATURES

Dynamic VAR compensation

Harmonic elimination

Load balancing

CONTROL FEATURES

Fully customizable harmonic compensation

Several ADF P100s can be combined for higher power

Insensitive to network conditions

Idle mode during low load (Standby)

Non-overloadable

Low response time

ADF Dashboard WUI (Web User Interface)

Floating grid frequency support

 

PHYSICAL FEATURES

Standard enclosure format system, according to IP20, EN50298, EN60529, EN50102

High short circuit capacity

Simple installation

Modular and scalable design

The ADF P100 is compatible with all three phase low voltage applications. It automatically eliminates harmonics and reactive displacement in a wide range of applications.

Further, the ADF P100 can be tailored to unusual applications requiring special optimizations. Some typical applications include:

  • Drive systems
  • Pump aplications
  • Offices and commercial buildings
  • Medical equipment
  • Industrial loads
  • UPS systems
  • Fans

Technical Specifications – ADF P100

Model ADF P100-50/480 ADF P100-75/480 ADF P100-90/480 ADF P100-120/480 ADF P100-150/480 ADF P100-90/690
Rated power * 35 / 42 kVA 52 / 62 kVA 62 / 75 kVA 83 / 100 kVA 104 / 125 kVA 94 /108 kVA
Compensation current capacity at 50/60 Hz 50 ARMS 75 ARMS 90 ARMS 120 ARMS 150 ARMS 90 ARMS
System voltage (± 10 %) 480 V (208 – 480 V) 690 V
(480 – 690 V)
Nominal frequency 45 – 65 Hz (Including floating frequency)
Number of phases 3 phase 3 wire
Connection type 3 phase without neutral (TN, TT, IT **)
Harmonic current compensated individual compensation up to 49th order
Rate of harmonic reduction better than 98%
Current compensation of cos φ up to 1.0
Expandability up to 15 ADF P100 units can be used in parallel
Response time < 1 ms
Power dissipation < 1600 W < 2535 W < 3180 W < 3155 W < 3225 W < 2969 W
Maximum air flow requirement < 600 m3/h
Noise level < 70 dB(A)
Environment 0 to 95 % RH non-condensing, max altitude 1000 m without derating
Operating temperature 0 to 50 °C, up to 40 °C without derating
Dimensions 230 x 1790 x 470 mm (W x H x D)
Weight 91 kg 91 kg 91 kg 105 kg 116 kg 150 kg
Enclosure color RAL 7035 (light grey) RAL 5017 (traffic blue)
Protection class IP20, IP21** according to IEC 529, other ratings upon request
Environmental conditions chemical 3C2, mechanical 3S2
Electromagnetic compatibility EN55011, Class B
Certificates CE, ABS, DNV GL

* Compensation power at 400 V / 480 V (600 V / 690 V) nominal voltage
** Option

 

Technical Specifications – ADF P100N

Model ADF P100N-100/415
Rated power 70 kVA
Compensation current capacity at 50/60 Hz 100 ARMS
Compensation current capacity at 50/60 Hz, Neutral 300 ARMS
Nominal voltage2 208 – 415 V
Nominal frequency1 45 – 65 Hz (Including floating frequency)
Number of phases 3 phase 4 wire
Connection type 3 phase with neutral (TN, TT)
Harmonic current compensated individual compensation up to 49th order
Rate of harmonic reduction better than 98%
Current compensation
of cos φ
up to 1.0
Expandability ADF P100 units can be used in parallel
Response time < 1 ms
Power dissipation < 2235 W
Maximum air flow requirement < 600 m3/h
Noise level < 70 dB
Environment 0 to 95% RH non-condensing, max altitude 1000 m
Operating temperature 0 to 50°C continous, < up to 40°C without derating
Dimensions 230 x 1790 x 470 mm (W x H x D)
Weight 160 kg
format color format RAL 7035 (gray), base RAL 5017 (blue)
Protection class IP20 according to IEC 529
Environmental conditions Chemical 3C2, Mechanical 3S2
Electromagnetic Compatibility EN 61000-6-2, EN 61000-6-4
Certificates CE
Art no 400 095

1 Please state your system voltage and line frequency when ordering